Input
Range/ Resolution
Accuracy
Sensor type
Standard output
Dual Display
LED Indication
Set point
Control action
Hysterisis
Setting
Monitoring
Supply Voltage
Cable
Operating Temperature
Sensor Housing
Enclosure Details
Protection Class
Cabinet Material
Cable Entry
Dimension
Mounting
Weight
Optional
|
Oxygen / Toxic / Combustible Gases, Please select from the Table
As specified in the table
± 1% of the full scale value
Electrochemical / Catalytic Pellister / Solid State / Infra Red based Sensors
Programmable Linear 4-20 / 20-4 mA O/P with respect to Gas concentration range
Upper :- 4 Digit of 13mm(H) Red LED display for 'Gas Concentration' indication
Lower :- 4 Digit of 13mm(H) Red LED display for 'Set Point Value’ of Alarm Relay-1/ Unit of Gas
LED Indication AL1 & AL2 for Relay, FLT for Fail-Safe Relay, PRG for Programming mode, INB for Service / Inhibit mode,
TST for Test mode, TX for Transmitting signal, RX for Receiving signal
2 No, Independent set point. For Alarm Relay-1 & Alarm Relay-2 with programmable latch & non-latch facility
LO / HI, HI / LO, LO/ Very LO, HI-Very HI, Programmable by user
0 to 100 counts, Individual setting for Alarm Relay-1 & Alarm Relay-2, programmable by user
Setting by 4 keys on front panel i.e. ‘SET / NEXT’, ‘UP’, ‘DOWN’ & ‘TEST / BACK’
I) By display : Sensor break/ open shows ‘oPEn’, under range shows ‘Undr’ & over range shows ‘ouEr’
ii) By Standard O/P current : Up scale current : 21mA, Down scale current : 3mA, selectable
18 to 36 VDC
1.5 sq. mm 3 Core, Flexible OR Armoured shielded cable
0 to 500C ± 5%, Relative Humidity: Below 95% non condensing
P.V.C. / P.P. / TEFLON material / SS304/SS316, Please select while ordering
OM - 1100 - WP ( Weatherproof ) OT - 1100 - FLP ( Flameproof )
IP-65 IP-65 for Gas Gr. IIA & IIB, ATEX, CCOE & CMRI Approved
Polycarbonate, gray colour Cast Alluminium alloy, LM-6 / C.I. Enclosure
Thermoplastic cable gland (IP 68) Double compression cable gland (Ex-Proof), ¾” ET type
with clamping range of 2.5 to 6.5mm
255mm(H) x 240mm(W) x 120mm(D) 180mm (H) x 205mm (W) x 110mm (D)
Wall Mounting / Stand Mounting Wall Mounting / Stand Mounting
Approx 2.0 Kg Approx 3.0 Kg
a) Isolated RS-485 Serial port with MODBUS RTU protocol output
b) SMARTLOG / SCADA SOFTWARE for online graph & data report for safety Audit
c) Flame Proof or Non Flame Proof Industrial Hooter, Hooter cum Flasher, Chart recorder, Cables,
PC Software, Gas Transmitters, 24 VDC power supply, Gas calibration kit
d) Optional 3 No, 1 NO-C-NC, 230 VAC/5A Potential Free Relay contacts for AL-l, AL-2, & Fail Safe Relay |