Measuring Parameter
Range
Resolution
Accuracy
Sensor Type
Sensor Probe Details
Loop Output
Display
Set Point
Setting
Monitoring -
Sensor Open Indication
Supply Voltage
Operating Temperature
Relative Humidity
Enclosure Detail
Protection Class
Cabinet Material
Cable Entry
Dimension
Mounting
Weight
Sensor Housing |
Humidity (% RH)
0 To 100 % RH
0.1 % RH
± 1.8 % of full scale value
Capacitive polymer sensing for high Please specify while inquiringsensing for Relative Humidity
Please Specify while Enquiry
Industrial Standard, 4 - 20 mA with permissible
0.5”, 3 ½ digit L.C.D Display / 0.4”, 4 Digit L.E.D Display
Two independent set points, AL1 & AL2 with blinking indication & Programmable Latch / Non-Latch facility;
only for indication purpose (There is no relay output)L.E.D display for Humidity
Setting by 4 keys on front panel i.e. ‘SET / NEXT’, ‘UP’, ‘DOWN’ & ‘TEST / BACK’
i) By Display : Shows “oPn”
ii) By Loop current :Up scale current : 22 mA, Down scale current :3.6 mA To 3.8 mA; programmable by user
14 To 36 VDC, normally 24 VDC, 25 mA
- 40 To 85 0C
Below 95% non condensing
WEATHERPROOF (WP) FLAMEPROOF (FLP)
IP- 65 IP-65, CMRI Approved for IIA & IIB Gas Group
Polycarbonate Colour Grey Cast Alluminium Alloy, LM-6,/C.I. Enclosure
Thermoplastic cable gland (IP-68) Double compression cable gland (Ex-Proof)¾” ET-type
215(H) X 240(W) X 120(D) in mm 300(H) X 250(W) X 110(D) in mm
Wall Mounting / Stand Mounting Wall Mounting / Stand Mounting
Approx. 2.5 Kg Approx. 4.0 Kg
P.V.C. / SS316, Please specifiy while ordering |